寒冷条件下高压电缆户外充油终端故障分析Failure Analysis of Outdoor Oil-Filled Terminal of High Voltage Cable in Low Temperature
宋鹏先,李帆,贺春,赵程,徐学刚,周凤争,魏佳
SONG Pengxian,LI Fan,HE Chun,ZHAO Cheng,XU Xuegang,ZHOU Fengzheng,WEI Jia
摘要(Abstract):
针对2021年1月发生在天津市的多起高压电缆充油终端故障,对故障发生的时间及现场情况进行调研,发现高压电缆户外充油终端故障多发于寒冷的冬季,观察故障现场发现绝缘油凝固、应力锥处电缆主绝缘击穿、应力锥内侧存在放电痕迹。根据调研结果,对不同种类的绝缘油的低温性能展开分析,研究结果表明,绝缘油凝固是造成冬季高压电缆户外充油终端故障的主要原因,而现行相关国家标准中对于绝缘油低温性能缺少相关规定,建议在标准中标明高压电缆户外充油终端绝缘油的最高倾点。
It mainly focuses on the multiple high voltage cable oil-filled terminal failures that occurred in Tianjin in January2021, and the time of the failure and the on-site situation are researched. The survey finds that the failures of the outdoor oil-filled terminal of high voltage cable mostly have occurred in cold winter. Observing the fault site, it is found that the insulation oil solidified, the cable main insulation broke down at the stress cone, and there are discharge traces inside the stress cone. According to the survey results, the low temperature performance of different types of insulating oils is analyzed. The research results show that the solidification of insulating oil is an important reason for the failure of the outdoor oil-filled terminal of high voltage cables in winter. However, the present relevant national standard lacks relevant regulations on the low temperature performance of insulating oil, and put forward that the highest pour point of insulating oil should be indicated in the standard.
关键词(KeyWords):
高压交联聚乙烯电缆;户外终端;绝缘击穿;硅油;聚异丁烯;低温性能
high voltage XLPE cable;outdoor terminal;insulating breakdown;silicone oil;polyisobutylene;low temperature performance
基金项目(Foundation): 国家自然科学基金重点项目“高压直流电缆附件绝缘老化与破坏机理及抑制方法研究”(51537008)
作者(Author):
宋鹏先,李帆,贺春,赵程,徐学刚,周凤争,魏佳
SONG Pengxian,LI Fan,HE Chun,ZHAO Cheng,XU Xuegang,ZHOU Fengzheng,WEI Jia
参考文献(References):
- [1]徐龙,赵艾萱,李嘉明,等.多次操作冲击对含刀痕缺陷10 k V电缆终端局部放电特性的影响[J].高电压技术,2020,46(2):673-681.
- [2]张静,程林,宋鹏先,等.基于硅油劣化特性对高压电缆终端热状态的测试分析[J].绝缘材料,2020,53(3):89-93.
- [3]孙永辉,王馥珏,韩宇泽.高压电缆终端击穿故障的分析与处理[J].兵器装备工程学报,2019,40(8):207-211.
- [4]于立佳,王银顺,朱承治,等.100 k V直流高温超导电缆终端应力锥设计[J].低温与超导,2020,48(4):42-46.
- [5]孙略,张沛红,李中原,等.高压直流电缆终端硅橡胶基非线性复合材料[J].高电压技术,2019,45(5):1654-1665.
- [6]胡飞,强卫,黄成龙,等.110 k V交联聚乙烯电缆模注熔接式终端的开发与应用[J].绝缘材料,2020,53(9):68-74.
- [7]张瑞敏,张沛红,宋淑伟,等.界面空间电荷对高压直流电缆终端电场分布的影响[J].高电压技术,2019,45(6):1762-1766.
- [8]李长明,伍国方,李春阳,等.XLPE绝缘高压直流电缆终端内缺陷对电场分布的影响[J].电机与控制学报,2018,22(12):62-67.
- [9]全国电线电缆标准化技术委员会.额定电压110 k V(Um=126 k V)交联聚乙烯绝缘电力电缆及其附件:GB/T11017.3-2014[S].北京:中国标准出版社,2015.
- [10]全国电线电缆标准化技术委员会.额定电压220 k V交联聚乙烯绝缘电力电缆及其附件:GB/T 18890.3-2015[S].北京:中国标准出版社,2016.
- [11]来国桥.有机硅产品合成工艺及应用[M].北京:化学工业出版社,2010.
- [12]李艾浓,王玉峰,马滨,等.聚异丁烯/甲基乙烯基硅橡胶互穿结构及其动态流变性能研究[J].中国胶黏剂,2020,29(5):10-14,28.