基于零序电压阶梯式增加引起发电机定子接地保护动作故障分析Fault Analysis of Generator Stator Grounding Protection Action with Step Increasing of Zero Sequence Voltage
文聆安,林永源,熊华兵
WEN Ling′an,LIN Yongyuan,XIONG Huabin
摘要(Abstract):
针对某电厂2号发电机机端零序电压突然出现阶梯式增加的异常变化,经现场试验及排查,排除了出口断路器外侧故障和发电机定子绝缘击穿引起的接地故障;进入发电机和出口断路器内部检查,发现出口断路器Ⅴ相发电机侧电容器出线套管伞裙上有明显黑褐色积油,判断电容器内部已放电击穿。对三相电容器全部换新处理,机组重新并网,运行参数正常。最后就故障原因进行分析,确定原因为:电容器出线套管与油箱锡焊密封处有裂纹漏油,触发发电机90%定子接地保护动作,机端零序电压呈阶梯式增加,造成电容器内部放电击穿,并对此提出了处理建议。
In view of the abnormal change of the zero sequence voltage at the end of the No.2 generator in a power plant,the outboard fault of the exit circuit breaker and the grounding fault caused by the breakdown of the insulation of the generator stator are eliminated by data analysis and field test. After the main transformer is shut down, the generator and the exit circuit breaker are checked inside, and it is found that there is obvious black and brown oil on the umbrella skirt of outlet tube of capacitor at the Ⅴ phase generator side of the exit circuit breaker. It is judged that the capacitor has been discharged and broken down. All three-phase capacitors are replaced and the unit is connected to the grid again, and the operating parameters are normal. Finally, the causes and countermeasures of two cracks in the soldering seals between the outlet tube of the faulted capacitor and the fuel tank are analyzed.
关键词(KeyWords):
出口断路器;发电机;接地保护;电容器;漏油;零序电压;阶梯式增加
exit circuit breaker;generator;grounding protection;capacitor;oil leak;zero sequence voltage;step increasing
基金项目(Foundation):
作者(Author):
文聆安,林永源,熊华兵
WEN Ling′an,LIN Yongyuan,XIONG Huabin
参考文献(References):
- [1]贺家李,李永丽,董新洲,等.电力系统继电保护原理[M].4版.北京:中国电力出版社,2010.
- [2]高春如,大型发电机组继电保护整定计算与运行技术[M].2版.北京:中国电力出版社,2010.
- [3]陈延枫,王艳,颜惠宇.电力系统继电保护技术[M].北京:中国电力出版社,2018.
- [4]杨正理,黄其新,王士政.电力系统继电保护原理及应用[M].北京:机械工业出版社,2010.
- [5]黎帅.一起发电机定子接地保护动作引起机组非停的分析[J].江西电力,2020,44(2):58-61.
- [6]黄晓鹏,丁永允,赵帅达,等.同一机组多次定子接地保护事故对比分析[J].东北电力技术,2019,40(8):48-51,55.
- [7]余银灰,王文明,孙炜.发电机断路器对单相基地故障影响的研究[J].电力安全技术,2018,20(4):52-55.
- [8]胡尧尧.一起发电机定子接地故障的分析与处理[J].电机技术,2021(1):43-47.
- [9]邹海龙,严鹏飞.发电机定子接地保护应用及实例分析[J].华电技术,2018,6(40):51-53.
- [10]中华人民共和国电力工业部.电力设备预防性试验规程:DL/T 596—1996[S].北京:中国电力出版社,1996.
- [11]廖维东,吴双杰.发电机出口断路器两侧电容器渗油缺陷分析及对策[J].云南水力发电,2020,36(1):183-184.
- [12]王振河,陈天,咸日常,等.电力电容器常见故障分析及预防措施[J].电力电容器与无功补偿,2020,41(2):42-46.
- [13]姜胜宝,倪学锋,林浩,等.高压电容器极间绝缘耐潮湿性能的试验研究[J].电力电容器与无功补偿,2019,40(1):46-48,58.
- [14]涂小涛,张征平,胡卫.发电机出口电容器缺陷引起定子接地保护动作诊断方法[J].电力系统自动化,2014,38(24):96-101.
- [15]王斯斯,刘宇,熊俊,等.一起500 kV电容式电压互感器电容击穿故障分析[J].广东电力,2017,30(1):126-130.