内蒙古电网复合绝缘子运行老化性能分析Performance Analysis on Operational Aging of Composite Insulators in Inner Mongolia Power Grid
赵建坤,车传强,燕宝峰,赵建利,赵雷,谢明佐
ZHAO Jiankun,CHE Chuanqiang,YAN Baofeng,ZHAO Jianli,ZHAO Lei,XIE Mingzuo
摘要(Abstract):
介绍了内蒙古电网复合绝缘子应用情况,抽取了一批不同电压等级、运行年限、生产厂家的复合绝缘子,对其外观、电气、机械及材料性能进行试验检测。结果表明,交流耐压试验、陡波前冲击耐受电压试验、机械破坏负荷试验合格率达100%,说明复合绝缘子早期应用出现的机械强度下降问题基本解决;憎水性试验、带护套芯棒水扩散试验、护套黏接强度试验合格率较低,反映运行复合绝缘子老化特征较为灵敏,建议将上述试验项目用于网内运行复合绝缘子抽检;喷水分级法用于运行复合绝缘子憎水性测试效果较好;热重分析、红外光谱分析等方法判定绝缘子伞裙早期老化程度效果良好,材料老化程度对复合绝缘子长期运行的影响仍需继续深入研究。
The application situation of composite insulators in Inner Mongolia power grid is introduced. A batch of compositeinsulators of different voltage levels, operating years, and manufacturers are selected, and their appearance, electrical,mechanical and material properties are comprehensively tested. The results show that the percent of pass of AC withstandvoltage test, steep-front impulse test, and mechanical failing load test reaches 100%, which shows that the problem ofmechanical strength decline in the early application of composite insulators is basically solved. The pass rate ofhydrophobicity test, sheathed mandrel water diffusion test, and sheath bonding strength test is low, reflecting that the agingcharacteristics of operating composite insulators are more sensitive. It is recommended that the above test items used for thesampling test of composite insulators running in the power grid. Water spray classification method is better forhydrophobicity test of running composite insulators. Methods such as thermogravimetric analysis and infrared spectrumanalysis are effective in judging the early aging degree of insulator umbrella skirts. The effect of material aging degree onthe long-term operation of composite insulators still needs to be further studied.
关键词(KeyWords):
输电线路;复合绝缘子;抽样检测;老化性能
transmisson lines;composite insulator;sampling test;aging performance
基金项目(Foundation): 内蒙古电力(集团)有限责任公司科技项目“复合绝缘子运行老化特性及瓷绝缘子机械电气性能检测技术研究”(2019-95)
作者(Author):
赵建坤,车传强,燕宝峰,赵建利,赵雷,谢明佐
ZHAO Jiankun,CHE Chuanqiang,YAN Baofeng,ZHAO Jianli,ZHAO Lei,XIE Mingzuo
参考文献(References):
- [1]梁曦东,高岩峰,王家福,等.中国硅橡胶复合绝缘子快速发展历程[J].高电压技术,2016,42(9):2888-2896.
- [2]闫康.基于在线自动检测装置的复合绝缘子憎水性评价[J].内蒙古电力技术,2019,37(4):97-100.
- [3]闫永利,闫军,郭福根,等.运行合成绝缘子电气及机械性能的试验研究[J].内蒙古电力技术,2004(3):7-10.
- [4]夏云峰,宋新明,何建宗,等.复合绝缘子用硅橡胶老化状态评估方法[J].电工技术学报,2019,34(增刊):440-448.
- [5]梁曦东,高岩峰.复合绝缘子酥朽断裂研究(一):酥朽断裂的主要特征、定义及判据[J].中国电机工程学报,2016,36(17):4778-4786.
- [6]李超红.复合绝缘子芯棒断裂研究现状[J].绝缘材料,2018,51(6):7-11.
- [7]姚莉娜,吴颖晖,王少华,等.挂网运行复合绝缘子的电气及力学性能研究[J].绝缘材料,2015,48(8):23-27.
- [8]电力行业绝缘子标准化技术委员会.标称电压高于1000 V架空线路用绝缘子使用导则第3部分:交流系统用棒形悬式复合绝缘子:DL/T 1000.3—2015[S].北京:中国电力出版社,2015.
- [9]电力行业绝缘子标准化技术委员会.标称电压高于1000 V交、直流系统用复合绝缘子憎水性测量方法:DL/T1474—2015[S].北京:中国电力出版社,2015.
- [10]电力行业绝缘子标准化技术委员会.聚合物绝缘子伞裙和护套用绝缘材料通用技术条件:DL/T 376—2019[S].北京:中国电力出版社,2019.
- [11]全国高电压试验技术和绝缘配合标准化技术委员会.绝缘配合第1部分:定义、原则和规则:GB 311.1—2012[S].北京:中国标准出版社,2013.
- [12]杨晓辉.基于傅立叶变换红外光谱测试的复合绝缘子老化评估方法研究[D].北京:华北电力大学,2013.