选取内蒙古电网不同输电线路多支在役复合绝缘子,利用扫描电子显微镜(SEM)、X射线能谱仪(EDS)、傅里叶红外光谱仪(FTIR)、邵氏硬度计及拉伸试验机等仪器对各系列复合绝缘子高压侧伞裙材料性能进行表征分析。结果表明,随着运行年限的增加,绝缘子伞裙表面粗糙度基本呈逐渐增大趋势,而C元素质量分数和Si-CH3峰面积则随运行时间的增加不断下降;此外,硅橡胶材料的老化对伞裙硬度、拉伸强度及断裂伸长率同样具有显著影响。最后,基于各特征参量测试结果建立寿命预测模型,并初步制订复合绝缘子老化性能判断依据。
Abstract:The author selects multiple in-service composite insulators from different transmission lines of Inner Mongolia Power Grid, and make an analysis of the material properties of high-voltage(HV) side shed from each series of composite insulators by SEM, EDS, FTIR, Shore durometer and tensile testing machine. The results show that with the increase of the operating time, the surface roughness of the shed shows a gradually increasing trend, while the mass fraction of element C and the peak area of Si-CH3 continuously decrease. In addition, the aging of silicone rubber materials also has a significant impact on the hardness, tensile strength, and elongation at break of sheds. Finally, a life prediction model based on the test results of various characteristic parameters is established, and a basis for judging the aging performance of composite insulators is also preliminarily proposed.
[1] 黄小浪.特高压输电线路中的复合绝缘子应用探讨[J].农村电气化,2022(11):80-81. HUANG Xiaolang. Discussion on application of composite insulators in UHV transmission lines[J]. Rural Electrification, 2022, 49(11): 80-81.
[2] 刘亨洋,顾哲屹.复合绝缘子在特高压输电线路中的应用[J].电子技术,2020,49(4):94-95. LIU Hengyang, GU Zheyi. Application of composite insulator in UHV transmission line[J]. Electronic Technology, 2020, 49(4): 94-95.
[3] FERNANDO M, GUBANSKI S M. Ageing of SIR insulators in coastal and inland tropical environment[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 2010, 17(2): 326-333.
[4] 乔路丽,蔺雨桐,李静,等.基于深度学习的绝缘子缺失检测方法研究[J].电网与清洁能源,2022,38(10):44-50. QIAO Luli, LIN Yutong, LI Jing, et al. Research on Insulator Loss Detection Based on Deep Learning[J]. Advances of Power System & Hydroelectric Engineering, 2022, 38(10): 44-50.
[5] 梁曦东,高岩峰,王家福,等.中国硅橡胶复合绝缘子快速发展历程[J].高电压技术,2016,42(9):2888-2896. LIANG Xidong, GAO Yanfeng, WANG Jiafu, et al. Rapid development of silicone rubber composite insulator in China[J]. High Voltage Engineering, 2016, 42(9): 2888-2896.
[6] MOGHADAM M K, TAHERI M, GHARAZI S, et al. A study of composite insulator aging using the tracking wheel test[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 2016, 23(3): 1805-1811.
[7] GUAN Z, ZHANG F, CHENG L, et al. Aging characterization and lifespan prediction of silicone rubber material utilized for composite insulators in areas of atypical warmth and humidity[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 2016, 23(6): 3547-3555.
[8] 王思华,陈龙,王军军,等.复合绝缘子伞套老化状态模糊综合评估[J].中国电力,2021,54(5):156-165. WANG Sihua, CHEN Long, WANG Junjun, et al. Fuzzy comprehensive evaluation of aging state of silicone rubber sheds of composite insulators[J]. Electric Power, 2021, 54(5): 156-165.
[9] 曾磊磊,张宇,曾鑫,等.复合绝缘子硅橡胶伞裙老化状态评估方法综述[J].电瓷避雷器,2022(2):139-145. ZENG Leilei, ZHANG Yu, ZENG Xin, et al. Aging state evaluation methods for silicone rubber sheds of composite insulators[J]. Insulators and Surge Arrests, 2022(2): 139-145.
[10] 周晨,周路遥,李特,等.浙江省内复合绝缘子断串及芯棒击穿故障分析[J].高压电器,2021,57(5):182-188. ZHOU Chen, ZHOU Luyao, LI Te, et al. Fault analysis on string fracture and core breakdown of composite insulator in Zhejiang province[J]. High Voltage Apparatus, 2021, 57(5): 182-188.
[11] 李鸿泽.复合绝缘子断串原因分析及防范措施[J].电力工程技术,2018,37(4):51-56. LI Hongze. Composite insulators fracture fault and preventing methods[J]. Jiangsu Electrical Engineering, 2018, 37(4): 51-56.
[12] 梁栋.±500 kV复合绝缘子断串原因与防范措施研究[J].电子元器件与信息技术,2020,4(10):76-77. LIANG Dong. Study on the causes and preventive measures of breakage of ± 500 kV composite insulators[J]. Electronic Component and Information Technology, 2020, 4(10): 76-77.
[13] 张素慧,滕玉林,谢金鹏,等.一起330 kV输电线路复合绝缘子断裂故障失效[J].电瓷避雷器,2023(5):164-170. ZHANG Suhui, TENG Yulin, XIE Jinpeng, et al. Fracture failure of composite insulator of 330 kV transmission line[J]. Insulators and Surge Arrests, 2023(5): 164-170.
[14] 吴旭翔,王少华,李特,等.一起220 kV复合绝缘子芯棒断裂事故分析[J].电工电气,2019(3):55-58. WU Xuxiang, WANG Shaohua, LI Te, et al. Analysis of a corerodfracture accident of 220 kV composite insulators[J]. Eletrotechnics Electric, 2019(3): 55-58.
[15] 郑建军,李铁,史贤达,等.蒙西电网220kV在运复合绝缘子材料老化性能研究分析[J].青海电力,2022,41(3):26-31. ZHENG Jianjun, LI Tie, SHI Xianda, et al. Investigation and analysis on aging performance of 220 kV in-service composite insulator materials in Mengxi Power Grid[J]. Qinghai Electric Power, 2022, 41(3): 26-31.
[16] 李勃铖,李稳,张稷,等.一起500 kV复合绝缘子断裂故障分析[J].浙江电力,2023,42(9):117-123. LI Bocheng, LI Wen, ZHANG Ji, et al. Cause analysis on fracture of a 500 kV composite insulator[J]. Zhejiang Electric Power, 2023, 42(9): 117-123.
[17] 王琳,侯涛,王得鹏,等.基于4G通信的接触网绝缘子在线监测装置研制[J].电网与清洁能源,2023,39(4):31-36,46. WANG Lin, HOU Tao, WANG Depeng, et al. Development of an On-Line Monitoring Device for Catenary Insulators Based on 4G Communication[J]. Power System and Clean Energy, 2023, 39(4): 31-36, 46.
[18] 胡大伟,苑经纬,刘桁宇,等.大气条件下复合绝缘子端部电晕放电产生的等离子体诊断方法研究[J].东北电力技术,2021,42(10):14-18. HU Dawei, YUAN Jingwei, LIU Hengyu, et al. Research on Diagnostic Method of Plasma Caused by Corona Discharge on Composite Insulator Top Under Atmosphere Conditions[J]. Northeast Electric Power Technology, 2021, 42(10): 14-18.
[19] 谢从珍.硅橡胶复合绝缘子伞裙优化研究[D].广州:华南理工大学,2010.
[20] 成立,梅红伟,王黎明,等.复合绝缘子用硅橡胶护套长时间老化特性及其影响因素[J].电网技术,2016,40(6):1896-1902. CHENG Li, MEI Hongwei, WANG Liming, et al. Study on Long-Term Aging Characteristics and Impact Factors for Silicone Rubber Sheath of Composite Insulators[J]. Power System Technology, 2016, 40(6): 1896-1902.
基本信息:
DOI:10.19929/j.cnki.nmgdljs.2024.0023
中图分类号:
引用信息:
[1]辛力坚, 王超, 燕宝峰等.在役复合绝缘子伞裙材料老化研究[J].内蒙古电力技术,2024,42(02):44-48.DOI:10.19929/j.cnki.nmgdljs.2024.0023.
基金信息:
内蒙古电力(集团)有限责任公司科技项目“极端污秽地区复合绝缘子选型方法及运维策略研究”(2023-5-32)